Chapter 3 - Installation and Wiring
GP-2400/2500/2600 Series User Manual 3-9
3.2.3 Grounding
(a) Exclusive Grounding (BEST)
*1
Connect the FG terminal found at the back of
the GP to an exclusive ground. [diagram (a)].
(b) Common Grounding (OK)
*1
• Check that the grounding re-
sistance is less than 100
.
• The SG and FG terminals are
connected internally in the
GP unit.
• When connecting the SG line
to another device, be sure
that the design of the system/
connection does not produce
a shorting loop.
• The grounding wire should
have a cross sectional area
greater than 2mm
2
. Create
the connection point as close
to the GP unit as possible,
and make the wire as short,
as possible. When using a
long grounding wire, replace
the thin wire with a thicker
wire, and place it in a duct.
(c) Common Grounding (Not OK)
Input and output signal lines must be separated from the power control cables for
operating circuits.
I
f this is not possible, use a shielded cable and connect the shield to the GP’s frame.
3.2.4 I/O Signal Line Placement
If exclusive grounding is not possible, use a
common connection point. [diagram (b)]
If the equipment does not function
properly when grounded, disconnect
the ground wire from the FG termi-
nal.
*1 Use a grounding resistance of less than 100W and a 2mm
2
or greater thickness wire,
or your country’s applicable standard. For details, contact your local GP distributor.
Do not use common grounding, since it can lead to an acci-
dent or machine breakdown.
CAUTION